Product overview
Sealed oil-immersed distribution transformers for 10 kV and 20 kV networks, with corrugated tanks and project-specific winding and tapping arrangements.
Get a quote JIADEST / 10 kV / 20 kV Oil-Immersed Distribution Transformers
Manufacturer’s series: S11 / S13 / S20 / S22
Sealed oil-immersed distribution transformers for 10 kV and 20 kV networks, with corrugated tanks and project-specific winding and tapping arrangements.
Search the complete technical catalog
Sealed oil-immersed distribution transformers for 10 kV and 20 kV networks, with corrugated tanks and project-specific winding and tapping arrangements.
Specify the required rated power in kVA or MVA, primary and secondary voltages, frequency, installation conditions and applicable project requirements. Consult the original technical sheets for the published design information.
| Parameter | Published specification |
|---|---|
| Voltage class | 10 kV / 20 kV |
| Series designations | S13, S20, S22 |
Designations are retained as published. Separate rows or variants with the same designation remain distinct in the relevant tables.
| Model | Rated capacity (kVA) | Voltage class (kV) | Scope / configuration note |
|---|---|---|---|
| S11-M-315/10 | 315 | 10 | Brochure / model-specific documentation; confirm selected configuration |
| S11-M-2000/10 | 2000 | 10 | Brochure / model-specific documentation; confirm selected configuration |
| S13-M-630/10 | 630 | 10 | Brochure / model-specific documentation; confirm selected configuration |
| S13-M-2500/10-NX3 | 2500 | 10 | Brochure / model-specific documentation; confirm selected configuration |
| S20-M-2500/10-NX2 | 2500 | 10 | Brochure / model-specific documentation; confirm selected configuration |
| S22-M-2500/10-NX1 | 2500 | 10 | Brochure / model-specific documentation; confirm selected configuration |
ENGINEERING SELECTION / INDUSTRY BENCHMARKS
Use these published international-market examples to discuss your efficiency target and network requirements.
| Rated power (kVA) | Voltage class scope (kV) | No-load loss P0 (W) | Load loss Pk (W) | Short-circuit impedance uk (%) |
|---|---|---|---|---|
| 1000 | Up to 24 | 693 | 7600 | 6 |
| 1600 | Up to 24 | 1080 | 12000 | 6 |
| 2500 | Up to 24 | 1575 | 18500 | 6 |
| 1000 | Up to 36 | 796 | 8360 | 6 |
| 1600 | Up to 36 | 1242 | 13200 | 6 |
| 2500 | Up to 36 | 1811 | 20350 | 6 |
The voltage-class limits above are source-table headings, not voltage ratios. P0 and Pk are different loss quantities. Compare ratings only with matching voltage class, frequency, loss evaluation conditions and test basis; request the applicable load-loss reference temperature.
Values transcribed from Eaton’s published liquid-immersed transformer technical tables , checked 2 November 2026. The IEC design standard and the EU efficiency requirements are separate specifications.
JIADEST / TECHNICAL SELECTION GUIDE
Start your specification with the reference ratings and configuration items below. Send the combination your project needs for engineering review.
S11 / S13 / S20 / S22 are industry series references. The applicable JIADEST model and design must be confirmed with the quotation.
| Parameter | Reference for your inquiry |
|---|---|
| Rated power references | 30–2,500 kVA; nominate the capacity required for your project. |
| Primary voltage references | 6, 6.3, 10, 11, 13.8, 22 or 33 kV; specify the actual rated voltage and insulation level. |
| Secondary voltage references | 0.4, 0.415 or 0.433 kV; other requirements can be submitted for review. |
| Number of phases | Three-phase reference configurations. |
| Rated frequency | Specify 50 Hz or 60 Hz; each rating requires a corresponding design. |
| Vector group | Dyn11 or Yyn0 reference arrangements; confirm against the system requirements. |
| Cooling method | ONAN reference configuration; other cooling duties require a separate review. |
| Tap changer / tapping range | Off-circuit reference: ±2 × 2.5%. Specify any different range or on-load requirement. |
| Winding material | Specify copper or aluminum; electrical and mechanical ratings must match the selected design. |
| Tank / insulating liquid | Specify hermetically sealed or conservator construction, and the required insulating liquid. |
| Site conditions | State ambient temperature, altitude, indoor/outdoor location and corrosion conditions. |
| Standards for review | Identify the applicable IEC 60076 requirements or the project-specified standard and edition. This guide does not establish conformity. |
19 REFERENCE CAPACITY RATINGS / 30–2,500 kVA
Each row is an illustrative starting point for an inquiry, not a confirmed stock model or a complete product datasheet. The voltage and frequency shown do not limit your project request; specify any required changes in the form.
| Rated power | Primary / secondary | Frequency | Next step |
|---|---|---|---|
| 30 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 50 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 63 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 80 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 100 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 125 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 160 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 200 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 250 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 315 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 400 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 500 kVA | 11 / 0.415 kV | 50 Hz | Request review |
| 630 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 800 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 1,000 kVA | 11 / 0.415 kV | 50 Hz | Request review |
| 1,250 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 1,600 kVA | 11 / 0.415 kV | 50 Hz | Request review |
| 2,000 kVA | 10 / 0.4 kV | 50 Hz | Request review |
| 2,500 kVA | 10 / 0.4 kV | 50 Hz | Request review |
Request these design-specific values with your quotation. They cannot be determined from the series name or rated capacity alone.
Prepared from public industry product information, with conflicting or design-specific performance values excluded. Industry examples do not verify JIADEST ratings or certifications.
DIMENSIONS / CONNECTIONS / SOURCE DATA
The original sheet retains all dimensioned drawings, connection diagrams, table footnotes and published values. It is supplied in its original language for direct verification against the English specification.
Open original sheet at native resolution
Original brochure technical sheet 2 TALK TO JIADEST
Use the exact model, voltage, current or power rating, duty cycle and drawing reference when requesting a quotation. Confirm source discrepancies and project-specific requirements in the approved technical agreement.